Mostrar el registro sencillo del ítem
Modelamiento eléctrico de Red Compacta en Media Tensión para determinar la Calidad de Suministro Eléctrico en el Distrito de Santa Leonor, Región Lima 2024.
| dc.contributor.advisor | Villalobos Cabrera, Jony | es_PE |
| dc.contributor.author | Miñope Alarcon, Junior Nicolas | es_PE |
| dc.date.accessioned | 2026-01-27T16:04:38Z | |
| dc.date.available | 2026-01-27T16:04:38Z | |
| dc.date.issued | 2025-11-06 | |
| dc.identifier.uri | https://hdl.handle.net/20.500.12893/16043 | |
| dc.description.abstract | Esta tesis aborda el modelamiento eléctrico de una red compacta en media tensión para mejorar la calidad del suministro eléctrico en el distrito de Santa Leonor, región Lima, Perú. El proyecto surge ante la problemática de interrupciones frecuentes debido al uso de conductores desnudos en áreas rurales y urbanas con vegetación densa y estructuras cercanas, lo que afecta la continuidad del servicio. La metodología aplicada es de tipo no experimental, enfocada en el diseño y modelamiento de un tramo de 463.78 metros con conductores semiaislados tipo AAAC Anaheim de 78.74 mm2, operando a 23 kV. Se implementaron protecciones eléctricas como fusibles tipo K de 65 A y descargadores de sobretensión de 20 kV para garantizar la seguridad y continuidad del suministro. Los indicadores de calidad considerados incluyen el SAIFI (frecuencia de interrupciones) y el SAIDI (duración de interrupciones). Los resultados muestran que la red compacta reduce significativamente la frecuencia y duración de las interrupciones, mejorando la confiabilidad del servicio. El presupuesto total del proyecto asciende a S/ 38,682.27, considerando costos de materiales, montaje (S/ 18,567.81) y transporte (S/ 7,350.00). La implementación de 13 sistemas de puesta a tierra PAT-0 y un sistema PAT-1 garantiza la protección ante fallas a tierra. La propuesta contribuye a la modernización del sistema eléctrico en Santa Leonor, mejorando la calidad de vida de sus habitantes al asegurar un suministro continuo y seguro. | es_PE |
| dc.description.abstract | This thesis addresses the electrical modeling of a compact medium-voltage network to improve the quality of electricity supply in the district of Santa Leonor, Lima region, Peru. The project arises from the frequent interruptions caused by the use of bare conductors in rural and urban areas with dense vegetation and nearby structures, which negatively impact service continuity. The applied methodology is non-experimental, focused on the design and modeling of a 463.78-meter section using semi-insulated AAAC Anaheim conductors of 78.74 mm2, operating at 23 kV. Electrical protections such as K-type fuses of 65 A and surge arresters of 20 kV were implemented to ensure safety and service continuity. The quality indicators considered include SAIFI (System Average Interruption Frequency Index) and SAIDI (System Average Interruption Duration Index). The results demonstrate that the compact network significantly reduces the frequency and duration of interruptions, improving the reliability of the service. The total project budget amounts to S/ 38,682.27, including material costs, assembly (S/ 18,567.81), and transportation (S/ 7,350.00). The installation of 13 grounding systems PAT-0 and one PAT-1 system ensures protection against ground faults. The proposal contributes to the modernization of the electrical system in Santa Leonor, enhancing the quality of life of its inhabitants by ensuring a continuous and safe electricity supply. | es_PE |
| dc.description.sponsorship | Cotrina Saavedra, | es_PE |
| dc.format | application/pdf | es_PE |
| dc.language.iso | spa | es_PE |
| dc.publisher | Universidad Nacional Pedro Ruiz Gallo | es_PE |
| dc.rights | info:eu-repo/semantics/openAccess | es_PE |
| dc.rights.uri | http://creativecommons.org/licenses/by-nc-sa/4.0/ | es_PE |
| dc.subject | Red compacta | es_PE |
| dc.subject | Media tensión | es_PE |
| dc.subject | Calidad del suministro eléctrico | es_PE |
| dc.subject | Interrupciones | es_PE |
| dc.subject | Santa Leonor | es_PE |
| dc.subject | Compact network | es_PE |
| dc.subject | Medium voltage | es_PE |
| dc.subject | Electricity supply quality | es_PE |
| dc.subject | Interruptions | es_PE |
| dc.title | Modelamiento eléctrico de Red Compacta en Media Tensión para determinar la Calidad de Suministro Eléctrico en el Distrito de Santa Leonor, Región Lima 2024. | es_PE |
| dc.type | info:eu-repo/semantics/bachelorThesis | es_PE |
| thesis.degree.name | Ingeniero Mecánico Electricista | es_PE |
| thesis.degree.grantor | Universidad Nacional Pedro Ruiz Gallo - Facultad de Ingeniería Mecánica y Eléctrica | es_PE |
| thesis.degree.discipline | Ingeniería Mecánica y Eléctrica | es_PE |
| dc.type.version | info:eu-repo/semantics/submittedVersion | es_PE |
| dc.publisher.country | PE | es_PE |
| dc.subject.ocde | http://purl.org/pe-repo/ocde/ford#2.02.01 | es_PE |
| renati.author.dni | 75480245 | |
| renati.advisor.dni | 16699530 | |
| renati.advisor.orcid | https://orcid.org/0000-0003-3643-5498 | es_PE |
| renati.type | http://purl.org/pe-repo/renati/type#tesis | es_PE |
| renati.level | http://purl.org/pe-repo/renati/nivel#tituloProfesional | es_PE |
| renati.discipline | 713076 | es_PE |
| renati.juror | Horna Torres, Segundo Abelardo | es_PE |
| renati.juror | Cotrina Saavedra, Carlos Javier | es_PE |
| renati.juror | Tapia Asenjo, Robinson | es_PE |